To upgrade to the i-Vu Pro v6.0 application
6 Enter the name of the four databases that were created in SQL Studio Manager on the new computer.
7 Enter the username and password that was created in SQL Studio manager for the new i-Vu v6.0 installation.
8 Click
Next
.
9 Confirm that you have backed up and click
Next
when the
Upgrade complete
message appears.
10 The upgrade process copies the necessary system files to your i-Vu Pro v6.0 installation directory and
performs the required database upgrade steps.
Upgrading drivers
When upgrading a v3.1 database, the drivers for the i-Vu Integrators are automatically updated to the
latest drivers. v3.1 drivers do not function in v6.0.
When upgrading a v4.2 database, a dialog lists all the current drivers and you can uncheck them if you
do not want them to be upgraded. v4.2 drivers will function in v6.0.
11 Enter a password and click
Next
to complete the database upgrade.
NOTE
If the 4 i-Vu® databases do not reside under the default instance of SQL, then the instance name must be
specified under the
Instance
column. The syntax for specifying the instance name of the SQL server is
<Database>;instance=<instance name>. For example, if the SQL instance name is hvac , the syntax for
the Instance field for the main database called iVu_Main would be iVu_Main;instance=hvac.
i-Vu® Application Carrier Proprietary and Confidential CARRIER CORPORATION ©2014
Rev. 3/21/2014 All rights reserved
31