To merge a mixed system to the i-Vu Plus v6.0 application
3 Click
OK
when you see the message
The system will be stopped and restarted. Do you wish to proceed?
The
Operation Status
message updates as the i-Vu application prepares and creates the backup. Wait for
Operation Status
to state
No Background Operations Currently Active
.,
4 Remove USB drive from the web server.
NOTES
A check of the USB drive will show a backup file named
system.backup
An error may be displayed under the
Management Tool
title stating
The USB device failed to mount and
initialize. Connect the USB drive to the first USB port
. In this case, try a different USB drive or try
rebooting the i-Vu web server, as there was an issue accessing the USB drive.
5 Exit from
Management Tool
.
6 You must reboot the web server before proceeding.
Install i-Vu® v6.0 software
Use the following steps to install the i-Vu® v6.0 application on
both
of your web servers, even the one you will no
longer use.
1 Remove the i-Vu® web server from the network by disconnecting the LAN cable.
2 Insert the i-Vu® v6.0 Installation DVD into the i-Vu® web server DVD drive or USB Installation drive into the
USB port on the front of the web server.
3 Shut down the i-Vu® web server by pushing the On/Off button
once
. Wait for the blue light to turn off (could
take as long as 2 minutes).
4 Press the On/Off button again to restart the web server. The installation begins automatically.
5 The Installation DVD ejects or the USB drive's light goes off when the installation is complete. This process
takes several minutes.
NOTE
Do not power off during the installation.
Connect and power up target i-Vu® web server
If you are currently using both a USB CCN and an Open Adapter, you must replace one of them with an external
router. i-Vu v6.0 application does not support 2 USB cables on the single web server.
1 If necessary, re-locate the i-Vu web server that you have chosen as the web server for i-Vu v6.0. For instance,
if you are using a USB Adapter cable, you most likely need to move the target web server with the largest
memory to the physical location of the cable.
2 Plug the power cable into the back of the i-Vu® web server and into an electrical outlet.
NOTE
We highly recommended using a UL Certified power surge/RFI suppression device.
3 Connect an Ethernet cable from the laptop computer’s network port, or the customer's LAN, to the Ethernet
jack on the back of the i-Vu® web server.
i-Vu® Application Carrier Proprietary and Confidential CARRIER CORPORATION ©2014
Rev. 3/21/2014 All rights reserved
18